JBY46 150 - 200 AMP Magnetic Latching Contactor

JBY 46 Magnalatch
Up to 60 VDC, 150 - 200 Amps

The MAGNA-LATCH TM Latched Low Voltage Disconnect Contactor is more compact than traditional low voltage disconnects. The permanent magnet holds the contact closed. Momentary power to the coil closes the contact, while a momentary reverse power signal to the coil opens the contact. The MAGNA-LATCH TM also uses the same bus bars available on traditional electrically held contactors.

Optional features of the MAGNA-LATCH TM include special coil voltage silver-plated bus bars, custom bus bars, mounting studs and nuts in bus bars, and additional auxiliary contacts. Screw coil terminals, side mounted feet for horizontal mounting and a rectifier for AC coil operation are additional optional features.

Benefits:
  • Coil heat is eliminated
  • Reduces need for redundant power control
  • 24 VDC units suitable for use on 48 VDC systems
  • Designed to remain closed for 20 years
  • Fail safe - contacts open or close only when appropriate signal is applied
  • Specifications +


    PERFORMANCE DATA
    Main Contact Data
    Resistive Load Rating, Continuous Duty 200 AMPS
    Inductive Load Rating, Continuous Duty 150 AMPS
    Current Rating By Reduced Duty Cycle
    70% Duty 180 AMPS
    60% Duty 195 AMPS
    50% Duty 225 AMPS
    40% Duty 240 AMPS
    30% Duty 270 AMPS
    Contact Voltage, Max.
    JBA460 & JBB460 48V D.C.
    JBA467 & JBB467 96V D.C.
    JBC460 & JBM460 48V D.C.
    JBC467 & JBM467 96V D.C.
    JBD460 & JBV460 48V D.C.
    JBD467 & JBV467 96V D.C.
    JBY460 48V D.C.
    JBY467 96V D.C.
    Contact Voltage Drop, Typical
    JBA460 & JBB460 <40mV
    JBD460 & JBV460 <50mV
    JBC460 & JBM460 (normally open contacts) <40mV
    JBC460 & JBM460 (normally closed contacts) <50mV
    ARC Rupture Currents Per UL 583
    JBA460 & JBL460 1200 AMPS at 48V D.C.
    JBA467 & JBL467 1200 AMPS at 96V D.C.
    JBC460 & JBM460* 1200 AMPS at 48V D.C.
    JBC467 & JBM467* 1200 AMPS at 96V D.C.
    JBD460 & JBV460 1200 AMPS at 48V D.C.
    JBD467 & JBV467 1200AMPS at 96V D.C.
    *Normally open contacts, not normally closed contacts  
    Overload Currents Per UL 508
    JBY460 & JBA460 & JBL460 300 AMPS at 60V D.C.
    JBC460 & JBD460 300 AMPS at 60 V D.C.
    JBM460 & JBV460 300 AMPS at 60V D.C.
    Coil Data
    Coil Power Dissipation  
    Intermittently duty coil 20-41 Watts
    Continuous duty coils 10-16 Watts
    Maximum pull-in voltage (coil at 25OC)  
    Intermittently duty coils <60% VDC Nominal
    Continuous duty coils <66% VDC Nominal
    Maximum drop-out voltage <25% VDC Nominal
    Operate Times - Typical
    Pull-in time (n/o contacts to close) <30ms
    Typical contact bounce period <5ms
    Drop-out time (n/o contacts to open)  
    No suppression <15ms
    Zener/Zener or Zener/Diode Suppression <15ms
    Varistor suppression <19ms
    Diode and resistor suppression 18-60ms
    Diode Suppression <75ms
    Main contact changeover time (JAC4600 & JAM4600)  
    Normally closed to normally open <10ms
    Normally open to normally closed <5ms
    Auxillary Contact Data
    Thermal current rating 5 AMPS
    Current capacity, resistive load 5A at 24V D.C.
    2A at 48V D.C.
    0.5A at 240V D.C.
    Miscellaneous Design Details
    Blow Out Magnets 48 - 96 VDC Contacts
    Temperature Range -20o C to +50o C
    Mechanical Life >3 x 10 5thpower
    IP Code: IP31 PER IEC 60529
    RoHS Compliant  
    Material Handling UL File Au2277
    Telecom UL File E161810