JBY46 150 - 200 AMP Magnetic Latching Contactor

JBY 46 Magnalatch
Up to 60 VDC, 150 - 200 Amps

The MAGNA-LATCH™ Latched Low Voltage Disconnect Contactor is more compact than traditional low voltage disconnects. The permanent magnet holds the contact closed. Momentary power to the coil closes the contact, while a momentary reverse power signal to the coil opens the contact. The MAGNA-LATCH™ also uses the same bus bars available on traditional electrically held contactors.

Optional features of the MAGNA-LATCH™ include special coil voltage silver-plated bus bars, custom bus bars, mounting studs and nuts in bus bars, and additional auxiliary contacts. Screw coil terminals, side mounted feet for horizontal mounting and a rectifier for AC coil operation are additional optional features.

Benefits:
  • Coil heat is eliminated
  • Reduces need for redundant power control
  • 24 VDC units suitable for use on 48 VDC systems
  • Designed to remain closed for 20 years
  • Fail safe - contacts open or close only when appropriate signal is applied
  • Specifications +


    PERFORMANCE DATA
    Main Contact Data
    Resistive Load Rating, Continuous Duty 200 AMPS
    Inductive Load Rating, Continuous Duty 150 AMPS
    Current Rating By Reduced Duty Cycle
    70% Duty 180 AMPS
    60% Duty 195 AMPS
    50% Duty 225 AMPS
    40% Duty 240 AMPS
    30% Duty 270 AMPS
    Contact Voltage, Max.
    JBA460 & JBB460 48V D.C.
    JBA467 & JBB467 96V D.C.
    JBC460 & JBM460 48V D.C.
    JBC467 & JBM467 96V D.C.
    JBD460 & JBV460 48V D.C.
    JBD467 & JBV467 96V D.C.
    JBY460 48V D.C.
    JBY467 96V D.C.
    Contact Voltage Drop, Typical
    JBA460 & JBB460 <40mV
    JBD460 & JBV460 <50mV
    JBC460 & JBM460 (normally open contacts) <40mV
    JBC460 & JBM460 (normally closed contacts) <50mV
    ARC Rupture Currents Per UL 583
    JBA460 & JBL460 1200 AMPS at 48V D.C.
    JBA467 & JBL467 1200 AMPS at 96V D.C.
    JBC460 & JBM460* 1200 AMPS at 48V D.C.
    JBC467 & JBM467* 1200 AMPS at 96V D.C.
    JBD460 & JBV460 1200 AMPS at 48V D.C.
    JBD467 & JBV467 1200AMPS at 96V D.C.
    *Normally open contacts, not normally closed contacts  
    Overload Currents Per UL 508
    JBY460 & JBA460 & JBL460 300 AMPS at 60V D.C.
    JBC460 & JBD460 300 AMPS at 60 V D.C.
    JBM460 & JBV460 300 AMPS at 60V D.C.
    Coil Data
    Coil Power Dissipation  
    Intermittently duty coil 20-41 Watts
    Continuous duty coils 10-16 Watts
    Maximum pull-in voltage (coil at 25OC)  
    Intermittently duty coils <60% VDC Nominal
    Continuous duty coils <66% VDC Nominal
    Maximum drop-out voltage <25% VDC Nominal
    Operate Times - Typical
    Pull-in time (n/o contacts to close) <30ms
    Typical contact bounce period <5ms
    Drop-out time (n/o contacts to open)  
    No suppression <15ms
    Zener/Zener or Zener/Diode Suppression <15ms
    Varistor suppression <19ms
    Diode and resistor suppression 18-60ms
    Diode Suppression <75ms
    Main contact changeover time (JAC4600 & JAM4600)  
    Normally closed to normally open <10ms
    Normally open to normally closed <5ms
    Auxillary Contact Data
    Thermal current rating 5 AMPS
    Current capacity, resistive load 5A at 24V D.C.
    2A at 48V D.C.
    0.5A at 240V D.C.
    Miscellaneous Design Details
    Blow Out Magnets 48 - 96 VDC Contacts
    Temperature Range -20o C to +50o C
    Mechanical Life >3 x 10 5thpower
    IP Code: IP31 PER IEC 60529
    RoHS Compliant  
    Material Handling UL File Au2277
    Telecom UL File E161810