PERFORMANCE DATA
|
|
Main Contact Data
|
| Resistive Load Rating, Continuous Duty |
400 AMPS |
| Inductive Load Rating, Continuous Duty |
300 AMPS |
|
|
|
Current Rating By Reduced Duty Cycle
|
| 70% Duty |
315 AMPS |
| 60% Duty |
340 AMPS |
| 50% Duty |
380AMPS |
| 40% Duty |
410 AMPS |
| 30% Duty |
475 AMPS |
|
Contact Voltage, Max.
|
| JCA460 & JCB460 |
48V D.C. |
| JCA467 & JCB467 |
96V D.C. |
| JCC460 & JCM460 |
48V D.C. |
| JcC467 & JCM467 |
96V D.C. |
| JCD460 & JCV460 |
48V D.C. |
| JCD467 & JCV467 |
96V D.C. |
| JCY460 |
48V D.C. |
| JCY467 |
96V D.C. |
|
Contact Voltage Drop, Typical
|
| JCA460 & JCB460 |
<40mV |
| JCD460 & JCV460 |
<50mV |
| JCC460 & JCM460 (normally open contacts) |
<40mV |
| JCC460 & JCM460 (normall closed contacts) |
<50mV |
|
ARC Rupture Currents Per UL 583
|
| JCA460 & JCL460 |
2500 AMPS at 48V D.C. |
| JCA467 & JCL467 |
1500 AMPS at 96V D.C. |
| JCC460 & JCM460* |
2500 AMPS at 48V D.C. |
| JCC467 & JCM467* |
1500 AMPS at 96V D.C. |
| JCD460 & JCV460 |
2500 AMPS at 48V D.C. |
| JCD467 & JCV467 |
1500 AMPS at 96V D.C. |
| *Normally open contacts, not normally closed contacts |
|
|
Overload Currents Per UL 508
|
| JCY460 & JCA460 & JCL460 |
600 AMPS at 60V D.C. |
| JCC460 & JCD460 |
600 AMPS at 60 V D.C. |
| JCM460 & JCV460 |
600 AMPS at 60V D.D. |
|
|
|
Coil Data
|
| Coil Power Dissipation |
|
| Intermittently duty coil |
31-70 Watts |
| Continuous duty coils |
14-20 Watts |
| Maximum pull-in voltage (coil at 25OC) |
|
| Intermittently duty coils |
<60% VDC Nominal |
| Continuous duty coils |
<66% VDC Nominal |
| Maximum drop-out voltage |
<25% VDC Nominal |
|
Operate Times - Typical
|
| Pull-in time (n/o contacts to close) |
<40ms |
| Typical contact bounce period |
<5ms |
| Drop-out time (n/o contacts to open) |
|
| No suppression |
<20ms |
| Zener/Zener or Zener/Diode Suppression |
<20ms |
| Varistor suppression |
<24ms |
| Diode and resistor suppression |
23-80ms |
| Diode Suppression |
<100ms |
| Main contact changeover time (JAC4600 & JAM4600) |
|
| Normally closed to normally open |
<11ms |
| Normally open to normall closed |
<6ms |
|
Auxillary Contact Data
|
| Thermal current rating |
5 AMPS |
| Current capacity, resistive load |
5A at 24V D.C.
2A at 48V D.C.
0.5A at 240V D.C. |
|
Miscileaneous Design Details
|
| Blow Out Magnets |
48 - 96 VDC Contacts |
| Temperature Range |
-20o C TO + 50o C |
| Mechanical Life |
>3 x 10 5thpower |
| IP Code: |
IP31 PER IEC 60529 |
| RoHS Compliant |
|
| Material Handling UL File |
Au2277 |
| Telecom UL File |
E161810 |