PERFORMANCE DATA
|
|
Main Contact Data
|
| Resistive Load Rating, Continuous Duty |
200 AMPS |
| Inductive Load Rating, Continuous Duty |
150 AMPS |
|
|
|
Current Rating By Reduced Duty Cycle
|
| 70% Duty |
180 AMPS |
| 60% Duty |
195 AMPS |
| 50% Duty |
225 AMPS |
| 40% Duty |
240 AMPS |
| 30% Duty |
270 AMPS |
|
Contact Voltage, Max.
|
| JBA460 & JBB460 |
48V D.C. |
| JBA467 & JBB467 |
96V D.C. |
| JBC460 & JBM460 |
48V D.C. |
| JBC467 & JBM467 |
96V D.C. |
| JBD460 & JBV460 |
48V D.C. |
| JBD467 & JBV467 |
96V D.C. |
| JBY460 |
48V D.C. |
| JBY467 |
96V D.C. |
|
Contact Voltage Drop, Typical
|
| JBA460 & JBB460 |
<40mV |
| JBD460 & JBV460 |
<50mV |
| JBC460 & JBM460 (normally open contacts) |
<40mV |
| JBC460 & JBM460 (normall closed contacts) |
<50mV |
|
ARC Rupture Currents Per UL 583
|
| JBA460 & JBL460 |
1200 AMPS at 48V D.C. |
| JBA467 & JBL467 |
1200 AMPS at 96V D.C. |
| JBC460 & JBM460* |
1200 AMPS at 48V D.C. |
| JBC467 & JBM467* |
1200 AMPS at 96V D.C. |
| JBD460 & JBV460 |
1200 AMPS at 48V D.C. |
| JBD467 & JBV467 |
1200AMPS at 96V D.C. |
| *Normally open contacts, not normally closed contacts |
|
|
Overload Currents Per UL 508
|
| JBY460 & JBA460 & JBL460 |
300 AMPS at 60V D.C. |
| JBC460 & JBD460 |
300 AMPS at 60 V D.C. |
| JBM460 & JBV460 |
300 AMPS at 60V D.C. |
|
|
|
Coil Data
|
| Coil Power Dissipation |
|
| Intermittently duty coil |
20-41 Watts |
| Continuous duty coils |
10-16 Watts |
| Maximum pull-in voltage (coil at 25OC) |
|
| Intermittently duty coils |
<60% VDC Nominal |
| Continuous duty coils |
<66% VDC Nominal |
| Maximum drop-out voltage |
<25% VDC Nominal |
|
Operate Times - Typical
|
| Pull-in time (n/o contacts to close) |
<30ms |
| Typical contact bounce period |
<5ms |
| Drop-out time (n/o contacts to open) |
|
| No suppression |
<15ms |
| Zener/Zener or Zener/Diode Suppression |
<15ms |
| Varistor suppression |
<19ms |
| Diode and resistor suppression |
18-60ms |
| Diode Suppression |
<75ms |
| Main contact changeover time (JAC4600 & JAM4600) |
|
| Normally closed to normally open |
<10ms |
| Normally open to normall closed |
<5ms |
|
Auxillary Contact Data
|
| Thermal current rating |
5 AMPS |
| Current capacity, resistive load |
5A at 24V D.C.
2A at 48V D.C.
0.5A at 240V D.C. |
|
Miscellaneus Design Details
|
| Blow Out Magets |
48 - 96 VDC Contacts |
| Temperature Range |
-20o C to +50o C |
| Mechanical Life |
>3 x 10 5thpower |
| IP Code: |
IP31 PER IEC 60529 |
| RoHS Compliant |
|
| Material Handling UL File |
Au2277 |
| Telecom UL File |
E161810 |